SC60HV PCS

DC side

Max. DC voltage
1500 V
Min. DC voltage
700 V
DC voltage range for nominal power
700 – 1300 V
Max. DC current
96.6 A
Max. DC power
67.5 kW

AC side (Grid)

AC output power
66 kVA @ 45 °C (113 °F) / 60 kVA @ 50 °C (122 °F)
Max. AC current
79.3 A
Nominal AC voltage
480 V
AC voltage range
422.4 – 528 V
Nominal grid frequency / Grid frequency range
60 Hz / 55 – 65 Hz
AC current THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power
> 0.99
Adjustable reactive power
-100% – 100%

AC side (Off-Grid)

Nominal AC voltage
400 V ± 3 %
AC voltage THD
< 3 % (Linear load)
Nominal voltage frequency / Voltage frequency range
60 Hz / 55 - 65 Hz
AC output power
66 kVA @ 45 °C / 60 kVA @ 50 °C

Efficiency

Max. charge efficiency
98.50 %
Max. discharge efficiency
98.60 %

Protection

Reverse polarity protection
DC switch
AC switch
Overvoltage protection
DC Type II / AC Type II
Grid monitoring
Ground fault monitoring
Insulation monitoring
Overheat protection

General Data

Dimensions
600 × 800 × 278 mm 23.6 × 31.5 × 11 in
Weight
75 kg 165.3 lb
Isolation method
Transformerless
Degree of protection
NEMA 4X
Operating ambient temperature range
-25 to 60 °C (> 50 °C derating) / -13 to 140 °F (> 122 °F derating)
Allowable relative humidity range (non-condensing)
0 – 100 %
Cooling method
Temperature controlled forced air cooling
Max. operating altitude
4000 m (> 3000 m derating) / 13123 ft (> 9843 ft derating)
Display
LED, Bluetooth + APP
Self-consumption at stop
< 20 W
Communication
RS485 / Ethernet / CAN
Communication protocol
Modbus-RTU / Modbus-TCP, CAN2.0B
Compliance
UL 1741, UL 1741 SA, Rule 21
Grid Support
L/HVRT, active & reactive power control, power ramp rate control
Type designation
SC60HV-10