SC2500HV PCS

DC side

Max. DC voltage
1500 V
Min. DC voltage
800 V
DC voltage range for nominal power
800 – 1300 V
Max. DC current
3508 A
Max. DC power
2806 kW

AC side (Grid)

AC output power
2750 kVA @ 45 °C / 2500 kVA @ 50 °C
Max. AC current
2886 A
Nominal AC voltage
550 V
AC voltage range
484 – 625 V
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
AC current THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power
> 0.99
Adjustable power factor
1 leading – 1 lagging
Adjustable reactive power
-100% – 100%

AC side (Off-Grid)

Nominal AC voltage
550 V
AC voltage range
484 – 625 V
AC voltage THD
< 3 % (Linear load)
DC voltage component
< 0.5 % Un (Linear balance load)
Unbalance load capacity
100 %
Nominal voltage frequency / Voltage frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz

Efficiency

Max. efficiency
98.80 %
Euro. efficiency
98.50 %

Protection

DC input protection
Load break switch + fuse
AC output protection
Circuit breaker
Overvoltage protection
DC Type II / AC Type II
Grid monitoring
Ground fault monitoring
Insulation monitoring
Overheat protection

General Data

Dimensions
2,991 × 2,591 × 2,438 mm
Weight
6,000 kg
Isolation method
Transformerless
Degree of protection
IP54
Auxiliary power supply
220 V, 2 kVA / 480 V, 30 kVA (optional)
Operating ambient temperature range
-30 to 60 °C (> 50 °C derating)
Allowable relative humidity range (non-condensing)
0 – 95 % (non-condensing)
Cooling method
Temperature controlled forced air cooling
Max. operating altitude
4000 m (> 2000 m derating)
Display
Touch screen
Communication
Standard: RS485, CAN, Ethernet; Optional: optical fiber
Compliance
CE, IEC 61727, IEC 62116, SGSF
Grid Support
L/HVRT, L/HFRT, active & reactive power control, power ramp rate control
Type designation
SC2500HV-10