SC2500U-MV | North America PCS

DC side

Max. DC voltage
1500 V
Min. DC voltage
800 V
DC voltage range for nominal power
800 – 1300 V
Max. DC current
3508 A
Max. DC power
2806 kW

AC side (Grid)

AC output power
2750 kVA @ 45 °C (113 °F) / 2500 kVA @ 50 °C (122 °F)
Max. AC current
2886 A
AC voltage range
34.5 kV
Nominal grid frequency / Grid frequency range
60 Hz / 55 – 65 Hz
AC current THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power
> 0.99
Adjustable power factor
1 leading – 1 lagging

AC side (Off-Grid)

Nominal AC voltage
550 V
AC voltage range
484 – 605 V
AC voltage THD
< 3 % (Linear load)
DC voltage component
< 0.5 % Un (Linear balance load)
Unbalance load capacity
100 %
Nominal voltage frequency / Voltage frequency range
60 Hz / 55 - 65 Hz

Efficiency

Max. efficiency
98.80 %
Euro. efficiency
98.50 %

Transformer

Transformer rated power
2500 kVA
Transformer max. power
2750 kVA
LV / MV voltage
0.55 kV / 10 – 35 kV
Transformer Vector
Dy1
Transformer cooling type
ONAN (Oil Natural Air Natural)
Oil type
Mineral oil (PCB free) or degradable oil on request

Protection

DC input protection
Load break switch + fuse
Inverter output protection
Circuit breaker
AC output protection
Load break switch + fuse
Overvoltage protection
DC Type II / AC Type II
Grid monitoring
Ground fault monitoring
Insulation monitoring
Overheat protection

General Data

Dimensions
6,058 × 2,896 × 2,438 mm 238.5 × 114 × 96 in
Weight
17,000 kg 37,478.6 lb
Degree of protection
Type 3R
Auxiliary power supply
220 V, 1.5 kVA / 110 V, 2.2kVA / 480 V, 30 kVA (optional)
Operating ambient temperature range
-30 to 60 °C (> 50 °C derating) / -22 to 140 °F (> 122 °F derating)
Allowable relative humidity range (non-condensing)
0 – 95 %
Cooling method
Temperature controlled forced air cooling
Max. operating altitude
1000 m (standard) / > 1000m (optional); 3280.8 ft (standard) / > 3280.8 ft (optional)
Display
Touch screen
Communication
Standard: RS485, CAN, Ethernet; Optional: optical fiber
Compliance
UL 1741, IEEE 1547, UL1741 SA, NEC Standard
Grid Support
L/HVRT, L/HFRT, active & reactive power control and power ramp rate control
Type designation
SC2500U-MV-10