SG1000/SG1250
Sales Area
APACEMEAIN
Cost Effiective
No need for inverter house on site
Integrated ventilation duct and auxiliary power supply
8 m² area easy for deployment and fast installation
10-foot standard shipping container
Easy Maintenance
Integrated current monitoring function for fast trouble shooting
Modular design easy for maintenance
Flexible
Complete grid support: LVRT, HVRT, ZVRT
IP54 protection degree suitable for harsh environment condition
Secured Yield
Efficient three-level topology, maximum system efficiency up to 99 %
1/2 MPPT, wide MPP voltage range.
No derating up to 50 ℃

Technical Data
Input (DC) SG1000 SG1250
Max. input voltage 1000 V  
Start voltage 500 V 540 V
Min. working voltage 460 V 520 V
Max. input current 2440 A 2712 A
MPP voltage range 460 - 850 V 520 - 850 V
No. of MPPTs 1 or 2  
No. of DC inputs 8 - 16  
Output (AC)
Nominal AC output power 1000 kW 1260 kW
Max. AC output apparent power 1100 kVA 1386 kVA
Max. inverter output current 2016 A 2222 A
Rated grid voltage 315 V 360 V
Grid voltage range 252 - 362 V 288 - 414 V
Nominal grid frequency 50 / 60 Hz  
Grid frequency range 45 - 55 Hz / 55 - 65 Hz  
THD < 3 % (at nominal power)  
DC current injection < 0.5 % In  
Power factor range 0.8 leading - 0.8 lagging  
Efficiency
Max.efficiency 99.00 %
Euro.efficiency 98.70 %
 
General Data
Dimensions (W*H*D) 2991*2591*2438 mm
Weight 4300 kg
Operating temperature range -35 to 60 ℃ (> 50 ℃ derating)
External auxiliary supply voltage(Opt.) 220 Vac, 2 kVA / Optional: 380 Vac, up to 15 kVA
Cooling concept Temperature controlled air-forced cooling
Protection Class IP54
Allowable relative humidity range 0 - 95 %, non -condensing
Max. operating altitude 5000 m (> 3000 m derating)
Communication Standard: RS485, Ethernet; Optional: Optical fiber
Protections & Functions
Anti-PID function Optional
Grid support functions LVRT, HVRT, ZVRT, Anti-Islanding, Active & reactive power regulation, PF control, Soft start / stop
DC input protection Circuit breaker 
AC output protection Circuit breaker
DC overvoltage protection Type II
AC overvoltage protection Type II
Grid monitoring Yes
Ground fault monitoring Yes
Overheat protection Yes
Insulation monitoring Yes