SG2000/2500
Cost Effiective
No need for inverter house on site
Integrated ventilation duct and auxiliary power supply
8 m² area easy for deployment and fast installation
10-foot standard shipping container
Easy Maintenance
Integrated current monitoring function for fast trouble shooting
Modular design easy for maintenance
Secured Yield
Efficient three-level topology, maximum system efficiency up to 99%
1/4 MPPT, wide MPP voltage range.
No derating up to 50℃
One inverter fails, the other units maintain safety operation
Flexible
Complete grid support: LVRT, HVRT, ZVRT
IP54 protection degree suitable for harsh environment condition

Technical Data
Input Side Data(DC) SG2000 SG2500
Max. input voltage 1000 V  
Start voltage 500 V 540 V
Min. working voltage 460 V 520 V
Max. input current 4880 A 5424 A
MPPT voltage range 460 - 850 V 520 - 850 V
No. of MPPTs 1 or 4  
No. of DC inputs  16 - 32  
Output (AC)
Nominal AC output power 2000 kW 2520 kW
Max. AC output apparent power 2200 kVA 2772 kVA
Max. inverter output current 4032 A 4444 A
Nominal grid voltage 315 V 360 V
Grid voltage range 252 - 362 V 288 - 414 V
Nominal grid frequency 50 / 60 Hz  
Grid frequency range 45 - 55 Hz / 55 - 65 Hz  
THD < 3% (at nominal power)  
DC current injection < 0.5% In  
Power factor range 0.8 leading - 0.8 lagging  
Efficiency
Max.efficiency 99.00%
Euro.efficiency 98.70%
General Data
Dimensions(W*H*D) 2991×2591×2438mm 117.8"*102.0"*96.0"
Weight 6.7 T 14771 lb
Operating ambient temperature range -35 to 60°C (>50°C derating) -31 - +140℉(>122℉ derating)
External auxiliary power supply 230 Vac, 2 kVA / Optional: 400 Vac, up to 15 kVA
Cooling method Temperature controlled air-forced cooling
Ingress protection rating IP54 NEMA3R
Allowable relative humidity range 0 - 95%, non -condensing
Max. operating altitude 6000 m (> 3000 m derating) 19685.0 ft(> 9842.5 ft derating)
Communication port Standard: RS485, Ethernet; Optional: Optical fiber
Inverters 4 x SG500MX 4 x SG630MX
Protections & Functions
Anti-PID function Optional
Grid Support Functions LVRT, HVRT, ZVRT, Anti-Islanding, Active & reactive power regulation, PF control, Soft start / stop
DC input protection Circuit breaker
AC output protection Circuit breaker
DC overvoltage protection Type II
AC overvoltage protection Yes
Grid monitoring Yes
Ground fault monitoring Yes
Overheat protection Yes
Insulation monitoring Yes