SG60KTL
Sales Area
APACEMEAINSAAF
High Yield
Max. efficiency 98.9 %, European efficiency 98.7 %
Long-term overload at 1.1 Pn
Full power operation without derating at 50 ℃
Easy O&M
Compact design and light weight for easy installation
Plug-in design of fan and SPD, convenient for
on-site maintenance
Integrated string current monitoring function for
fast trouble shooting
Saved Investment
Max. DC/AC ratio more than 1.4
Integrated DC combiner box and DC/AC overvoltage protection
Grid Support
Compliance with standards: IEC 62109, IEC
61727, IEC 62116, VDE0126-1-1, G59/3,
VDE-AR-N-4105, VDE-AR-N-4120, BDEW
Low/High voltage ride through (L/HVRT)
Active & reactive power control and power
ramp rate control

Technical Data
Inpt (DC) SG60KTL
Max PV input voltage 1000 V
Min. PV input voltage / Startup input voltage 570 V / 620 V
Nominal input voltage 710 V
MPP voltage range 570 - 950 V
MPP voltage range for nominal power 570 - 850 V
No. of independent MPP inputs 1
Max. number of PV strings per MPPT 14
Max. PV input current 120 A
Max. current for input connector 12 A
Max. DC short-circuit current 140 A
Output (AC)
Nominal AC power (at 50 ˚C) 60000 W
Max. AC output at PF=1 (at 50 ˚C) 60000 W
Max. AC apparent power (at 50 ˚C) 60000 VA
Max. AC output current 96 A
Nominal AC voltage 3 / N / PE or 3 / PE, 230 / 400 V
AC voltage range 310 - 480 V
Nominal grid frequency / Grid frequency range 50 Hz / 45 - 55 Hz, 60 Hz / 55 - 65 Hz
THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal powe / Adjustable power factor > 0.99 / 0.8 leading - 0.8 lagging
Feed-in phases / Connection phases 3 / 3
Efficiency
Max. efficiency / Euro. efficiency 98.9 % / 98.7 %
Protection
DC reverse connection protection Yes
AC short-circuit protection Yes
Leakage current protection Yes
Grid monitoring Yes
DC switch / AC switch Yes / No
DC fuse Yes (positive, 15A)
PV string current monitoring Yes
Overvoltage protection DC Type II / AC Type III
General Data
Dimensions (W*H*D) 634*932*267 mm 25.0''*36.7''*10.5''
Weight 60 kg 132.3 lb
Isolation method Transformerless
Degree of protection IP65
Night power consumption < 1 W
Operating ambient temperature range -25 to 60 ℃ (> 50 ℃ derating) -13 °F to 140 °F (> 122 °F derating)
Allowable relative humidity range (non-condensing) 0 - 100 %
Cooling method Smart forced air cooling
Max. operating altitude 4000m (>3000m derating) 13123 ft (>9843 ft derating)
Display / Communication Graphic LCD / RS485
DC connection type MC4 (Max. 6mm²)
AC connection type Screw clamp terminal (Max. 150 mm² )
Compliance CEA, IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683,
VDE0126-1-1, G59/3, VDE-AR-N-4105, VDE-AR-N-4120, BDEW,
IEC 61000-3-11/-12, EN 50438, UTE C 15-712-1/07.13
Grid support LVRT, HVRT, active & reactive power control and power ramp rate control
Type designation SG60KTL-182