SG250HX-US

.. Datasheet Published PDF English

High Yield

 

  • 12 MPPTs with max. efficiency 99%
  • Compatible with bifacial module
  • Built-in Anti-PID and PID recovery function

Low Cost

 

  • Compatible with Al and Cu AC cables
  • DC 2 in 1 connection enabled
  • Power line communication (PLC)
  • Reactive power at night function

Smart O&M

 

  • Touch free commissioning and remote firmware upgrade
  • Online IV curve scan and diagnosis*
  • Fuse free design with smart string current monitoring

Proven Safety

 

  • Integrated Arc fault circuit protection
  • NEMA 4X protection and C5 anti-corrosion grade
  • Type II SPD for both DC and AC
North America String Inverter
Max. operating altitude
4000 m (> 3000 m der atin g) 13123 ft (> 9843 ft derating)
Max. PV input voltage
1500 V
Min. PV input voltage / Startup input voltage
600 V / 600 V
MPP voltage range for nominal power
860 V – 1300 V
No. of independent MPP inputs
12
Max. PV input current
26 A * 12
Max. AC output current
180.5 A
AC voltage range
680 – 880V
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 57 – 63 Hz
THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
> 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases
3 / 3
Cooling method
Smart forced air cooling
Allowable relative humidity range (non-condensing)
0 – 100 %
Display
LED, Bluetooth+APP
Nominal AC voltage
3 / PE, 800 V
Isolation method
Transformerless
Max. DC short-circuit current
50 A * 12
Night power consumption
< 2 W
Nominal input voltage
1080 V
Max. current for input connector
30 A
DC reverse connection protection
Yes
AC short-circuit protection
Yes
Leakage current protection
Yes
DC switch
Yes
AC switch
No
PV string current monitoring
Yes
PID recovery function
No
Arc fault circuit interrupter (AFCI)
Yes
Islanding Protection
No
PV reverse connection protection
No
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off
Nominal AC output power
250 kVA @ 30 ℃ / 225 kVA @ 40 ℃ / 200 KVA @ 50 ℃

SG60KTL

.. Datasheet Published PDF English

High Yield

  • Max. efficiency 98.9 %, European efficiency 98.7 %
  • Long-term overload at 1.1 Pn
  • Full power operation without derating at 50 ℃

Saved Investment

  • Max. DC/AC ratio up to 1.4
  • Integrated DC combiner box and DC/AC overvoltage protection

Easy O&M

  • Compact design and light weight for easy installation
  • Plug-in design of fan and SPD, convenient for on-site maintenance
  • Integrated string current monitoring function for fast trouble shooting

Grid Support

  • Compliance with standards: IEC 62109, IEC 61727, IEC 62116, VDE0126-1-1, G59/3, VDE-AR-N-4105, VDE-AR-N-4120, BDEW
  • Low/High voltage ride through (L/HVRT)
  • Active & reactive power control and power ramp rate control
Brasil (PT) Latin America (ESP) String Inverter
Max. operating altitude
4000 m (> 3000 m derating)
Max. PV input voltage
1000 V
Min. PV input voltage / Startup input voltage
570 V / 620 V
MPP voltage range for nominal power
570 – 850 V
No. of independent MPP inputs
1
Max. PV input current
120 A
Max. AC output power
60000 W
Max. AC output current
96 A
AC voltage range
310 – 480 V
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
> 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases
3 / 3
Cooling method
Smart forced air cooling
Allowable relative humidity range (non-condensing)
0 – 100 %
Display
Graphic LCD
Nominal AC voltage
3 / N / PE or 3 / PE, 230 / 400 V
Isolation method
Transformerless
Max. DC short-circuit current
140 A
Night power consumption
< 1 W**
Nominal input voltage
710 V
Max. number of PV strings per MPPT
14
Max. current for input connector
12 A
DC reverse connection protection
No
AC short-circuit protection
No
Leakage current protection
No
DC switch
No
AC switch
No
PV string current monitoring
No
PID recovery function
No
Arc fault circuit interrupter (AFCI)
No
Islanding Protection
No
PV reverse connection protection
No
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off

SG36KTL-M

.. Datasheet Published PDF English

High Yield

  • Max. Efficiency 98.5%, European Efficiency 98.3%
  • 3 MPPT, Max. DC / AC ratio up to 1.4
  • Operation at rated power even under conditions 45 m horizontal mounting due to efficient design heat dissipation

Saved Investment

  • Integrated combiner box, DPS DC and AC system low cost

Easy O&M

  • String current monitoring function for quick troubleshooting
  • Compact design, low weight for quick installation
  • DPS device and designed fans plug-in for easy field maintenance

Grid Support

  • Complies with Standards: IEC 62109-1 / - 2, IEC 62103, IEC 61727, IEC 62116, EN 61000-6- 2 / -3, BDEW, G59 / 3, VDE 0126-1-1 / 4105 / 0124-100
  • Network support including: LVRT, HVRT, ZVRT, anti-islanding, active power regulation and reactive, power factor control FP and start / stop
Brasil (PT) Latin America (ESP) String Inverter
Max. operating altitude
4000 m (> 3000 m desclassificação)
Max. PV input voltage
1100 V
Min. PV input voltage / Startup input voltage
200 V / 250 V
MPP voltage range for nominal power
500 – 850 V
No. of independent MPP inputs
3
Max. PV input current
88A (33A/33A/22A)
Max. AC output power
36000 W
Max. AC inverter output current
53.5 A
AC voltage range
310 – 480 V
Nominal grid frequency / Grid frequency range
50 Hz / 60 Hz / 45 – 55 Hz / 55 – 65 Hz
THD
< 3 % (a potência nominal)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
> 0.99 / 0.8 adiantado – 0.8 atrasado
Feed-in phases / Connection phases
3 / 3
Cooling method
Resfriamento com ar forçado inteligente
Allowable relative humidity range (non-condensing)
0 – 100 %
Display
LCD gráfico / RS485
Nominal AC voltage
3 / PE or 3 / N / PE, 230 / 400 V
Isolation method
Transformerless
Max. DC short-circuit current
96 A
Night power consumption
< 2 W
Nominal input voltage
585 V
Max. number of PV strings per MPPT
3 / 3 / 2
Max. current for input connector
12 A
DC reverse connection protection
No
AC short-circuit protection
No
Leakage current protection
Yes
DC switch
Yes
AC switch
Yes
PV string current monitoring
No
PID recovery function
No
Arc fault circuit interrupter (AFCI)
No
Islanding Protection
No
PV reverse connection protection
Yes
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off

30CX | AUSTRALIA

.. Datasheet Published PDF English

High Yield

  • 3 MPPTs with max. efficiency 98.6%
  • Compatible with bifacial module
  • Built-in PID recovery function

Low Cost

  • Compatible with Al and Cu AC cables
  • DC 2 in 1 connection enabled
  • Cable free communication with optional Wi-Fi

Smart O&M

  • Touch free commissioning and remote firmware upgrade
  • Online IV curve scan and diagnosis
  • Fuse free design with smart string current monitoring

Proven Safety

  • IP66 and C5 anti-corrosion grade
  • Type II SPD for both DC and AC
  • Satisfied global safety and grid code
Europe String Inverter
Max. operating altitude
4000 m (> 3000 m derating)
Max. PV input voltage
1100 V
Min. PV input voltage / Startup input voltage
200V / 250 V
MPP voltage range for nominal power
550 – 850 V
No. of independent MPP inputs
3
Max. PV input current
78 A
Max. AC output power
29.9 KVA
Max. AC output current
43.15 A
AC voltage range
312 – 528 V
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
> 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases
3 / 3
Cooling method
Smart forced air cooling
Allowable relative humidity range (non-condensing)
0 – 100 %
Display
LED, Bluetooth+APP
Nominal AC voltage
3 / N / PE, 230 / 400 V
Isolation method
Transformerless
Max. DC short-circuit current
120 A
Night power consumption
≤2 W
Nominal input voltage
585 V
Max. number of PV strings per MPPT
3
Max. current for input connector
30 A
DC reverse connection protection
Yes
AC short-circuit protection
Yes
Leakage current protection
Yes
DC switch
No
AC switch
No
PV string current monitoring
Yes
PID recovery function
Yes
Arc fault circuit interrupter (AFCI)
No
Islanding Protection
No
Additional information
Q at night
Yes
PV reverse connection protection
No
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off

SG250HX

.. Datasheet Published PDF English Whitepaper Published PDF English

Smart O&M

  • Touch free commissioning and remote
  • Firmware upgrade
  • Online IV curve scan and diagnosis
  • Fuse free design with smart string current
  • Monitoring

High Yield

  • 12 MPPTs with max. efficiency 99%
  • Compatible with bifacial module
  • Built-in Anti-PID and PID recovery
  • Function

Low Cost

  • Compatible with Al and Cu AC cables
  • DC 2 in 1 connection enabled
  • Q at night function

Proven Safety

  • IP66 and C5 protection
  • Type II SPD for both DC and AC
  • Compliant with global safety and grid code
Asia & Pacific Europe String Inverter
Max. operating altitude
4000 m (> 3000 m derating)
Max. PV input voltage
1500 V
Min. PV input voltage / Startup input voltage
600 V / 600 V
MPP voltage range for nominal power
860 V – 1300 V
No. of independent MPP inputs
12
Max. PV input current
26 A * 12
Max. AC output power
250 kVA @ 30 ℃ / 225 kVA @40 ℃/200 KVA @50℃
Max. AC output current
180.5 A
AC voltage range
680 – 880V
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
> 0.99 / 0.8 leading – 0.8 lagging
Cooling method
Smart forced air cooling
Allowable relative humidity range (non-condensing)
0 – 100 %
Display
LED, Bluetooth+APP
Nominal AC voltage
3 / PE, 800 V
Isolation method
Transformerless
Max. DC short-circuit current
50 A * 12
Night power consumption
< 2 W
Nominal input voltage
1080 V
Max. number of PV strings per MPPT
2
Max. current for input connector
30 A
DC reverse connection protection
Yes
AC short-circuit protection
Yes
Leakage current protection
Yes
DC switch
Yes
AC switch
Yes
PV string current monitoring
Yes
PID recovery function
Yes
Arc fault circuit interrupter (AFCI)
No
Islanding Protection
No
PV reverse connection protection
No
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off

SG33/55CX-US | North America

.. Datasheet Published PDF English

High Yield

  • 4 MPPTs with max. efficiency 98.9%
  • Compatible with bifacial module
  • Built-in PID recovery function

Smart O&M

  • Touch free commissioning and remote firmware upgrade 
  • Online IV curve scan and diagnosis 
  • Fuse free design with smart string current monitoring 

Low Cost

  • DC/AC ratio more than 1.5
  • Compatible with AI and Cu AC cables
  • Flexible installation from vertical to horizontal 

Proven Safety

  • NEMA 4X and C5 protection
  • Type II SPD for both DC and AC
  • Compliant with UL safety and grid code
North America String Inverter
Max. operating altitude
4000 m (> 3000 m derating)
Max. PV input voltage
1000 V
Min. PV input voltage / Startup input voltage
200 V / 200 V
MPP voltage range for nominal power
500 – 850 V
No. of independent MPP inputs
4 | 6
Max. PV input current
26 A * 4 | 26 A * 6
Max. AC output power
33 kVA @ 45 ℃ (113 ℉) / 30 kVA @ 50 ℃ (122 ℉) | 55 kVA @ 45 ℃ (113 ℉) / 50 kVA @ 50 ℃ (122 ℉)
Max. AC output current
39.7 A | 66.2 A
AC voltage range
422 – 528 V
Nominal grid frequency / Grid frequency range
60 Hz / 55 – 65 Hz
THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
>0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases
3 / 3
Cooling method
Smart forced air cooling
Allowable relative humidity range (non-condensing)
0 – 100%
Display
LED, Bluetooth + APP
Nominal AC voltage
3 / N/PE, 277 / 480 V
Isolation method
Transformerless
Max. DC short-circuit current
40 A * 4 |. 40 A * 6
Night power consumption
< 2 W
Nominal input voltage
710 V
Max. number of PV strings per MPPT
2 / 2 / 2 / 2 | 2 / 2 / 2 / 2 / 2 / 2
Max. current for input connector
15 A
DC reverse connection protection
Yes
AC short-circuit protection
Yes
Leakage current protection
Yes
DC switch
Yes
AC switch
Yes
PV string current monitoring
Yes
CEC efficiency
98.50 %
PID recovery function
No
Arc fault circuit interrupter (AFCI)
Yes
Islanding Protection
No
PV reverse connection protection
No
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off

SG33/40/50CX

.. Datasheet Published PDF English Manual Published PDF English Quick Manual Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English

HIGH YIELD

  • 3 MPPTs with max. efficiency 98.6%
  • Compatible with bifacial PV modules
  • Built-in PID recovery function

LOW COST

  • Compatible with Al and Cu AC cables
  • DC 2 in 1 connection enabled
  • Cable free communication with optional Wi-Fi

SMART O&M

  • Touch free commissioning and remote firmware upgrade
  • Online IV curve scan and diagnosis
  • Fuse free design with smart string current monitoring

PROVEN SAFETY

  • IP66 and C5 protection
  • Type II SPD for both DC and AC
  • Compliant with global safety and grid codes
Asia & Pacific Europe Latin America (ESP) Brasil (PT) String Inverter
Max. operating altitude
4000 m (> 3000 m derating)
Max. PV input voltage
1100 V
Min. PV input voltage / Startup input voltage
200 V / 250 V
MPP voltage range for nominal power
550 – 850 V
No. of independent MPP inputs
3 | 4 | 5
Max. PV input current
78 A | 104 A | 130 A
Max. AC output power
36.3 kVA @ 40 °C / 33 kVA @ 45 °C | 44 kVA @ 40 ℃ / 40 kVA @ 45 ℃ | 55 kVA @ 40 ℃ / 50 kVA @ 45 ℃
Max. AC output current
55.2 A | 66.9 A | 83.6 A
AC voltage range
312 – 528 V
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
> 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases
3 / 3
Cooling method
Smart forced air cooling
Allowable relative humidity range (non-condensing)
0 – 100 %
Display
LED, Bluetooth+APP
Nominal AC voltage
3 / N / PE, 230 / 400 V
Isolation method
Transformerless
Max. DC short-circuit current
120 A | 160 A | 200 A
Night power consumption
≤2 W
Nominal input voltage
585 V
Max. number of PV strings per MPPT
2
Max. current for input connector
30 A
DC reverse connection protection
Yes
AC short-circuit protection
Yes
Leakage current protection
Yes
DC switch
Yes
AC switch
No
PV string current monitoring
Yes
PID recovery function
Yes
Arc fault circuit interrupter (AFCI)
No
Islanding Protection
Yes
PV reverse connection protection
No
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off

SG110CX

.. Datasheet Published PDF English Manual Published PDF English Quick Manual Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English Certificate Published PDF English

HIGH YIELD

  • 9 MPPTs with max. efficiency 98.7%
  • Compatible with bifacial PV modules
  • Built-in PID recovery function

LOW COST

  • Compatible with Al and Cu AC cables
  • DC 2 in 1 connection enabled
  • Cable free communication with optional Wi-Fi

SMART O&M

  • Touch free commissioning and remote firmware upgrade
  • Online IV curve scan and diagnosis
  • Fuse free design with smart string current monitoring

PROVEN SAFETY

  • IP66 and C5 protection
  • Type II SPD for both DC and AC
  • Compliant with global safety and grid codes
Asia & Pacific Brasil (PT) Europe Latin America (ESP) String Inverter
Max. operating altitude
4000 m (> 3000 m derating)
Max. PV input voltage
1100 V
Min. PV input voltage / Startup input voltage
200 V / 250 V
MPP voltage range for nominal power
550 – 850 V
No. of independent MPP inputs
9
Max. PV input current
234 A
Max. AC output power
110 kVA @ 45 °C / 100 kVA @ 50 °C
Max. AC output current
158.8 A
AC voltage range
312 – 528 V
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power / Adjustable power factor
> 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases
3 / 3
Cooling method
Smart forced air cooling
Allowable relative humidity range (non-condensing)
0 – 100 %
Display
LED, Bluetooth+APP
Nominal AC voltage
3 / N / PE, 230 / 400 V
Isolation method
Transformerless
Max. DC short-circuit current
360 A
Night power consumption
≤2 W
Nominal input voltage
585 V
Max. number of PV strings per MPPT
2
Max. current for input connector
30 A
DC reverse connection protection
Yes
AC short-circuit protection
Yes
Leakage current protection
Yes
DC switch
Yes
AC switch
No
PV string current monitoring
Yes
PID recovery function
Yes
Arc fault circuit interrupter (AFCI)
No
Islanding Protection
Yes
PV reverse connection protection
No
DC main output load switch
Off
PV specific application SPD
Off
PV SPD failure monitoring
Off
PV self power supply for internal loads
Off
Communication port
Off
Current and voltage monitoring for each string
Off