SG2500HV-20

Sales Area
Asia Pacific EMEA India, Sri Lanka & Bangladesh Mexico
Saved Investment
Low transportation and installation cost due to 10-foot container design
DC 1500 V system, low system cost
Integrated LV auxiliary power supply
Night Static Var Generator (SVG) function
High Yield
Advanced three-level technology, max.efficiency 99 %
Effective cooling, full power operation at 50 ℃
Max. DC/AC ratio up to 1.5
Easy O&M
Integrated current and voltage monitoring function for online analysis and fast trouble shooting
Modular design, easy for maintenance
Convenient external LCD

Technical Data

Input (DC)
Max. PV input voltage 1500V
Min. PV input voltage / Startup input voltage 800 V / 840 V
MPP voltage range for nominal powe 800 – 1300 V
No. of independent MPP inputs 1
No. of DC inputs 18
Max. PV input current 3508 A
Max. DC short-circuit current 4210 A
PV array configuration Negative grounding or floating
Output (AC)
Max. AC output power 2750 kVA@ 45 ˚C / 2500 kVA@ 50 ˚C
Max. AC output current 2886 A
Nominal AC voltage 550 V
AC voltage range 495 – 605 V
Nominal grid frequency / Grid frequency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal power / Adjustable power factor > 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases 3 / 3
Efficiency
Inverter Max. efficiency / Inverter Euro. efficiency 99.0 % / 98.7 %
Protection
DC input protection Load break switch + fuse
AC output protection Circuit breaker
Overvoltage protection DC Type I + II / AC Type II
Grid monitoring / Ground fault monitoring Yes / Yes
Insulation monitoring Yes
Overheat protection Yes
Night SVG function Yes
Anti-PID function Optional
General Data
Dimensions (W*H*D) 2991*2591*2438 mm
Weight 6.5 T
Isolation method Transformerless
Degree of protection IP54
Auxiliary power supply Optional:Max. 40 kVA
Operating ambient temperature range -35 to 60 ℃ (> 50 ℃ derating)
Allowable relative humidity range (non-condensing) 0 – 95 %
Cooling method Temperature controlled forced air cooling
Max. operating altitude 4000 m (> 2000 m derating)
Display Touch screen
Communication Standard: RS485, Ethernet; Optional: optical fiber
Compliance CE, IEC 62109, IEC 61727, IEC 62116
Grid support Night SVG function, L/HVRT, active & reactive power control and power ramp rate contro
Type designation SG2500HV-20

Product Consultation

Online Consulting