SG80KTL-M
Sales Area
Asia Pacific

High Yield
• | Max. efficiency 99 %, European efficiency 98.7 % |
• | 4 MPPT, adaptable to complex installation applications |
• | Long-time overload at 1.1 Pn at 45 ℃, full power operation at 50 ℃ |
• | PID recovery function |

Easy O&M
• | Integrated string current monitoring function for fast trouble shooting |
• | Compact design and light weight for easy installation |

Saved Investment
• | 16 DC inputs, max. DC/AC up to 1.3 |
• | Integrated tracking system power supply and communication interface |

Grid Support
• | Comply with IEC 61727, IEC 62116 |
• | Low/High voltage ride through (L/HVRT) |
• | Active & reactive power control and power ramp rate control |
Technical Data
Input (DC) | ||
Max. PV input voltage | 1100 V | |
Min. PV input voltage / Startup input voltage | 200 V / 250 V | |
Nominal input voltage | 585 V | |
MPP voltage range | 200 – 1000 V | |
MPP voltage range for nominal power | 500 – 850 V | |
No. of independent MPP inputs | 4 | |
Max. number of PV strings per MPPT | 4 / 4 / 4 / 4 | |
Max. PV input current | 176 A (44 A / 44 A / 44 A / 44 A) | |
Max. current for input connector | 12 A | |
Max. DC short-circuit current | 192 A (48 A / 48 A / 48 A / 48 A) |
Output (AC) | ||
AC output power | 88000 VA @ 45 ℃ / 80000 kVA @ 50 ℃ | |
Max. AC output current | 94.1 A | |
Nominal AC voltage | 3 / PE, 540 V | |
AC voltage range | 432 - 594 V | |
Nominal grid frequency / Grid frequency range | 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz | |
THD | < 3 % (at nominal power) | |
DC current injection | < 0.5 % In | |
Power factor at nominal power / Adjustable power factor | > 0.99 / 0.8 leading – 0.8 lagging | |
Feed-in phases / Connection phases | 3 / 3 |
Efficiency | ||
Max. efficiency / Euro. efficiency | 99.0 % / 98.7 % |
Protection | ||
DC reverse connection protection | Yes | |
AC short-circuit protection | Yes | |
Leakage current protection | Yes | |
Grid monitoring | Yes | |
DC switch / AC switch | Yes / No | |
DC fuse | Yes (positive, 15A) | |
PV string current monitoring | Yes | |
PID recovery function | Yes | |
Overvoltage protection | DC Type II / AC Type II |
General Data | ||
Dimensions (W*H*D) | 690*720*285 mm | |
Weight | 67 kg | |
Isolation method | Transformerless | |
Degree of protection | IP65 | |
Night power consumption | < 2 W | |
Operating ambient temperature range | -25 to 60 ˚C (> 50 ˚C derating) | |
Allowable relative humidity range (non-condensing) | 0 – 100 % | |
Cooling method | Smart forced air cooling | |
Max. operating altitude | 4000 m (> 3000 m derating) | |
Display / Communication | LED, Bluetooth + APP / RS485 | |
DC connection type | MC4 (Max. 6 mm²) | |
AC connection type | OT terminal (Max. 120 mm²) | |
Compliance | IEC 62109, IEC 61727, IEC 62116 | |
Grid support | LVRT, HVRT, active & reactive power control and power ramp rate control | |
Type designation | SG80KTL-M-10 |