SG80KTL-M

Sales Area
Asia Pacific
High Yield
Max. efficiency 99 %, European efficiency 98.7 %
4 MPPT, adaptable to complex installation applications
Long-time overload at 1.1 Pn at 45 ℃, full power operation at 50 ℃
PID recovery function
Easy O&M
Integrated string current monitoring function for fast trouble shooting
Compact design and light weight for easy installation
Saved Investment
16 DC inputs, max. DC/AC up to 1.3
Integrated tracking system power supply and communication interface
Grid Support
Comply with IEC 61727, IEC 62116
Low/High voltage ride through (L/HVRT)
Active & reactive power control and power ramp rate control

Technical Data

Input (DC)
Max. PV input voltage 1100 V
Min. PV input voltage / Startup input voltage 200 V / 250 V
Nominal input voltage 585 V
MPP voltage range 200 – 1000 V
MPP voltage range for nominal power 500 – 850 V
No. of independent MPP inputs 4
Max. number of PV strings per MPPT 4 / 4 / 4 / 4
Max. PV input current 176 A (44 A / 44 A / 44 A / 44 A)
Max. current for input connector 12 A
Max. DC short-circuit current 192 A (48 A / 48 A / 48 A / 48 A)
Output (AC)
AC output power 88000 VA @ 45 ℃ / 80000 kVA @ 50 ℃
Max. AC output current 94.1 A
Nominal AC voltage 3 / PE, 540 V
AC voltage range 432 - 594 V
Nominal grid frequency / Grid frequency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal power / Adjustable power factor > 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases 3 / 3
Efficiency
Max. efficiency / Euro. efficiency 99.0 % / 98.7 %
Protection
DC reverse connection protection Yes
AC short-circuit protection Yes
Leakage current protection Yes
Grid monitoring Yes
DC switch / AC switch Yes / No
DC fuse Yes (positive, 15A)
PV string current monitoring Yes
PID recovery function Yes
Overvoltage protection DC Type II / AC Type II
General Data
Dimensions (W*H*D) 690*720*285 mm
Weight 67 kg
Isolation method Transformerless
Degree of protection IP65
Night power consumption < 2 W
Operating ambient temperature range -25 to 60 ˚C (> 50 ˚C derating)
Allowable relative humidity range (non-condensing) 0 – 100 %
Cooling method Smart forced air cooling
Max. operating altitude 4000 m (> 3000 m derating)
Display / Communication LED, Bluetooth + APP / RS485
DC connection type MC4 (Max. 6 mm²)
AC connection type OT terminal (Max. 120 mm²)
Compliance IEC 62109, IEC 61727, IEC 62116
Grid support LVRT, HVRT, active & reactive power control and power ramp rate control
Type designation SG80KTL-M-10

Product Consultation