SC500TL/SC630TL

High Yield
Advanced three-level technology, max. efficiency 99%
Effective forced air cooling, 1.1 overload capacity, no derating up to 55°C
Various charge and discharge mode, flexible for battery configuration
Easy O&M
Integrated current & voltage monitoring function for online analysis and fast trouble shooting
Modular design and all components front accessible, easy for maintenance
Integrated auxiliary power supply panels for external devices
ESS Applications
Typical applations: peak shaving, energy, shifting, frequency regulation, capacity firming
Bidirectional power conversion system with full four-quadrant operation
Battery charge & dis-charge management , black start function and VSG integrated
Grid Support
Compliance with IEC 61727, IEC 62116, SGSF
Dynamic grid voltage and frequency support
L/HVRT,L/HFRT,soft start/stop, specified power factor control and reactive power support

Technical Data

DC side SC500TL SC630TL
Max. DC voltage 1000 V
Min. DC voltage 520 V 580 V
DC voltage range for nominal power 520 – 850 V 580 – 850 V
Max. DC current 1077 A 1217 A
Max. DC power 560 kW 706 kW
AC side (Grid)    
AC output power 550 kVA @ 50 ˚C / 500 kVA @ 55 ˚C 693 kVA @ 55 ˚C / 630 kVA @ 50 ˚C
Max. AC current 882 A 1000 A
Nominal AC voltage 360 V 400 V
AC voltage range 315 – 396 V 350 – 440 V
Nominal grid frequency / Grid frequency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
AC current THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal power / Adjustable power factor > 0.99 / 1 leading – 1 lagging
Adjustable reactive power -100% – 100%
AC side (Off-Grid)    
Nominal AC voltage 360 V 400 V
AC voltage range 315 – 396 V 350 – 440 V
AC voltage THD < 3 % (Linear load)
DC voltage component < 0.5 % Un (Linear balance load)
Unbalance load capacity 100 %
Voltage dynamic range ≤ 10% (Resistive load jump from 0 to 100 %)
AC side (VSG)    
Nominal AC voltage 360 V 400 V
Voltage command range 350 – 360 V 390 – 400 V
Frequency command range 49 – 51 Hz / 59 – 61 Hz
Active power command range -500 – 500 kW -630 – 630 kW
Reactive power command range -500 – 500 kVar -630 – 630 kVar
Efficiency    
Max. efficiency / Euro. efficiency 99 % / 98.7 %
Protection    
DC input protection Load break switch + fuse
AC output protection Circuit breaker
Overvoltage protection DC Type II / AC Type II
Grid monitoring / Ground fault monitoring Yes / Yes
Insulation monitoring Yes
Overheat protection Yes
General Data    
Dimensions (W×H×D) 1005*1915*835 mm
Weight 800 kg
Isolation method Transformerless
Degree of protection IP21
Operating ambient temperature range -30 to 65 ˚C (> 55 ˚C derating)
Allowable relative humidity range (non-condensing) 0 – 95 % (non-condensing)
Cooling method Temperature controlled forced air cooling
Max. operating altitude 5000 m (> 4000 m derating)
Display Touch screen
Communication Standard: RS485, CAN, Ethernet; Optional: optical fiber
Compliance CE, IEC 61727, IEC 62116, SGSF
Grid support L/HVRT, L/HFRT, active & reactive power control and power ramp rate control
Type designation SC500TL-10 SC630TL-10

Product Consultation