SC1000KU

Sales Area
Asia Pacific USA & Canada South America Sub-Saharan Africa
System Features
Multiple discharge/charge control modes
Designed for high voltage battery systems
Fast and accurate power response
Effective cooling, 1.1 overload capacity, no derating up to 122 ℉

Technical Data

DC Data
DC voltage range 810 – 1200 V
Max. DC current 1358 A
Grid Data
Nominal AC power 1000 kW
Max. AC power(long time operation) 1100 kVA
Max. AC current 1176 A
Max. THD of current < 3 % (at nominal power)
DC component < 0.5 %
Nominal grid voltage 540 V
Grid voltage range 475 – 594 V
Nominal grid frequency 60 Hz
Grid frequency range 55 – 65 Hz
Power factor at nominal power > 0.99
Power factor range 0.8 (lagging) – 0.8 (leading)
Efficiency
Max. efficiency 98.4 %
General Data
Dimensions (W×H×D) 1606 × 2065 × 960 mm / 63.2" × 81.3" × 37.8"
Weight 1400 kg / 3086 lbs.
Ingress protection rating IP 21 / NEMA 2
Operating temperature range -30 – 50 ℃ / -22 – 122 ℉
Relative humidity 0 – 95 % (Non-condensing)
Max. working altitude 3000 m (> 2,000 m derating) / 9843' (> 6,562' derating)
Display Touch screen
Cooling concept Temperature-controlled forced air cooling
Isolation Transformer
Power consumption at stop < 127 W
Noise < 70dB @ 1 m
Communication port RS485, Ethernet, CAN
Communication protocol Modbus RTU, Modbus TCP, IEC104
Certificates UL 1741, UL1741 SA (pending), IEEE 1547, IEEE 1547.1, CSA C22.2 No. 107.1-01, NEC code

Product Consultation

Online Consulting