SC50HV

High Yield
Advanced three-level technology, max. efficiency 98.5%
Effective forced air cooling, 1.1 overload capacity, no derating up to 50°C
Wide DC voltage operation window, flexible for battery configuration
Easy O&M
Compact design and light weight for easy installation
Easy site commissioning & monitoring via APP
Scalable system configuration, extend to MW power range
ESS Applications
Battery charge & dis-charge management integrated
Bidirectional power conversion system with full fourquadrant operation
EPS function design, can support the electrical equipment when the power grid fails
Compatible with high voltage battery system, low system cost
Grid Support
Compliance with IEC61727, IEC 62116
Grid support including L/HVRT, soft start/stop, specified power factor control and reactive power support

Technical Data

DC side
Max. DC voltage 1500 V
Min. DC voltage 580 V
DC voltage range for nominal power 580 – 1300 V
Max. DC current 96.6 A
Max. DC power 56 kW
AC side (Grid)
AC output power 55 kVA @ 45 ˚C / 50 kVA @ 50 ˚C
Max. AC current 79.3 A
Nominal AC voltage 400 V
AC voltage range 360 – 440 V
Nominal grid frequency / Grid frequency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
AC current THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal power / Adjustable power factor > 0.99 / 1 leading – 1 lagging
Adjustable reactive power -100% – 100%
AC side (Off-Grid)
Nominal AC voltage 400 V ± 3 %
AC voltage THD < 3 % (Linear load)
Nominal voltage frequency / Voltage frequency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
AC output power 55 kVA @ 45 ˚C / 50 kVA @ 50 ˚C
Efficiency
Max. charge efficiency 98.4 %
Max. discharge efficiency 98.5 %
Protection
Reverse polarity protection Yes
DC switch Yes
AC switch Yes
Overvoltage protection DC Type II / AC Type II
Grid monitoring / Ground fault monitoring Yes / Yes
Insulation monitoring Yes
Overheat protection Yes
General Data
Dimensions (W*H*D) 600*850*280 mm
Weight 75 kg
Isolation method Transformerless
Degree of protection IP65
Operating ambient temperature range -25 to 60 ˚C (> 50 ˚C derating)
Allowable relative humidity range (non-condensing) 0 – 100 %
Cooling method Temperature controlled forced air cooling
Max. operating altitude 4000 m (> 3000 m derating)
Display LED, Bluetooth + APP
Self-consumption at stop < 20 W
Communication RS485 / Ethernet / CAN
Communication protocol Modbus-RTU / Modbus-TCP, CAN2.0B
Compliance IEC 62109-1, IEC 62477.1, IEC 61727, IEC 62116, AS/NZS 4777.2:2015, AS/NZS 62040.1.1:2003
Grid support L/HVRT, active & reactive power control and power ramp rate control
Type designation SC50HV-10

Product Consultation

Online Consulting