The WiNet-S module firmware contains hardcoded MQTT credentials. This vulnerability could allow an attacker to send arbitrary commands to an inverter, leading to unauthorized control of Sungrow energy devices.
Affected Versions
Vulnerability Rating
CVE-2024-50692:8.1(AV:N/AC:H/PR:N/UI:N/S:C/C:L/I:L/A:H)
The scoring is based on the CVSS 3.1 standard. The scoring criteria can be referenced at
(https://www.first.org/cvss/calculator/3.1)
Mitigation and Remediation
Recommended Action: Customers should upgrade to firmware version WINET-SV200.001.00.P028 or higher.
Patch Release: Available now.
Temporary Fix: Restrict network access to MQTT ports until an upgrade is completed.
Exploitation Status
No known exploitation in the wild.
Acknowledgments
This vulnerability was discovered and reported by Forescout Technologies.
Statement
All software updates, patches, and documentation provided by Sungrow Power Supply Co., Ltd. are the proprietary work of Sungrow. These materials may only be used for product maintenance and security improvements. Any unauthorized modification, distribution, decompilation, or reverse engineering is strictly prohibited.
Sungrow makes no express or implied warranties regarding the information provided, including but not limited to warranties of merchantability, fitness for a particular purpose, or non-infringement. Sungrow shall not be liable for any direct, indirect, incidental, or consequential damages arising from the use of this document or associated software.